Figure 4-23. Checking voltage regulator setting.
specified range, remove the pipe plug (fig. 4-23) from
Note. Either terminal is satisfactory for
regulator cover and note the position of the plastic screw
this check provided a lead is connected to it.
slot beneath the plug. The slot will be lined up with one
of the divisions or lines cast in the regulator cover.
(3) Compare the voltage obtained in step (2)
Each division represents a voltage differential of 0.3
with voltage table 4-4. Ambient temperature is the
volt. Add or subtract 0.3 volt for each division from the
temperature of the air measured 1/4 inch from the
zero mark to the specified voltage limits in table 4-4.
regulator cover.
(4) If the actual voltage is not within the
Table 4-4. Voltage Table
Ambient
65
85
105
125
temperature
145
(Deg F)
Normal
14.1
13.9
13.7
13.5
13.4
Voltage
to
to
to
to
to
Setting
14.9
14.7
14.5
14.3
14.2
(Volts)
(5) If the voltmeter reading does not fall
(b) If the battery is consistently
within the specified limits outlined in table 4-4, replace
undercharged, (evidenced by the inability to crank the
the regulator. If the reading does fall within the
engine) at the regulator's present setting, increase the
prescribed limits, but the battery is either overcharged or
voltage setting by 0.3 volt and check for improved
undercharged, the regulator should be adjusted as
condition over a reasonable service period. If necessary,
outlined in the next step.
repeat this process until the battery remains charged
(6) Voltage setting adjustment.
with a minimum use of water.
(a) the battery uses too much water at
b. Removal.
the voltage regulator's present setting, reduce the
(1) Tag and disconnect the leads to the
voltage setting by 0.3 volt, one division on cover, and
voltage regulator.
check for decreased battery water usage over a
(2) Remove three capscrews lockwashers,
reasonable period of time. If necessary, repeat this
and nuts; remove the voltage regulator.
process until the battery remains charged with a
c. Installation. Install regulator by direct reversal of
minimum use of water.
removal.